NIBE S2125-16 3X400V
air-to-water monobloc · refrigerant R290 · 3x400V 50Hz · family S2125
Machine-readable: https://bedandbot.it/p/nibe-s2125-16-3x400v.json
| Property | Conditions | Value | Source |
|---|---|---|---|
| Cooling capacity | A35/W18, non_dichiarato load | 13.62 kW | NIBE “Capacity / power input / EER (kW/kW/-) at maximum flow 35 / 18 °C 8.68 / 2.60 / 3.34 8.68 / 2.60 / 3.34 13.62 / 3.46 / 3.93 13.62 / 3.46 / 3.93” |
| Cooling capacity | A35/W7, non_dichiarato load | 9.74 kW | NIBE “Cooling 35 / 7 °C 6.69 / 2.41 / 2.77 6.69 / 2.41 / 2.77 9.74 / 3.16 / 3.08 9.74 / 3.16 / 3.08” |
| COP | A-7/W35, partial load | 2.77 | NIBE “Heating -7 / 35 °C 4.72 / 1.72 / 2.74 7.23 / 2.73 / 2.65 10.31 / 3.72 / 2.77 12.03 / 4.56 / 2.64” |
| COP | A2/W35, partial load | 4.66 | NIBE “Capacity / power input / COP (kW/kW/-) at nominal flow 2 / 35 °C 3.20 / 0.72 / 4.44 3.67 / 0.85 / 4.32 6.58 / 1.41 / 4.66 7.38 / 1.59 / 4.63” |
| COP | A7/W35, partial load | 5.55 | NIBE “7 / 35 °C 3.15 / 0.61 / 5.16 3.67 / 0.70 / 5.24 5.10 / 0.92 / 5.55 5.10 / 0.92 / 5.55” |
| COP | A7/W45, partial load | 4.12 | NIBE “7 / 45 °C 2.97 / 0.76 / 3.90 3.35 / 0.85 / 3.94 4.85 / 1.18 / 4.12 4.85 / 1.18 / 4.12” |
| EER | A35/W18, non_dichiarato load | 3.93 | NIBE “Capacity / power input / EER (kW/kW/-) at maximum flow 35 / 18 °C 8.68 / 2.60 / 3.34 8.68 / 2.60 / 3.34 13.62 / 3.46 / 3.93 13.62 / 3.46 / 3.93” |
| EER | A35/W7, non_dichiarato load | 3.08 | NIBE “Cooling 35 / 7 °C 6.69 / 2.41 / 2.77 6.69 / 2.41 / 2.77 9.74 / 3.16 / 3.08 9.74 / 3.16 / 3.08” |
| Energy class | 35 °C application | A+++ classe | NIBE “The product’s room heating efficiency class A+++ / A++ A+++ / A+++ A+++ / A+++ A+++ / A+++” |
| Energy class | 55 °C application | A+++ classe | NIBE “The product’s room heating efficiency class A+++ / A++ A+++ / A+++ A+++ / A+++ A+++ / A+++” |
| Seasonal space heating energy efficiency (ηs) | average climate, 35 °C application | 210 % | HP Keymark 012-C700272 “η s 210 % 160 %” |
| Seasonal space heating energy efficiency (ηs) | colder climate, 35 °C application | 176 % | HP Keymark 012-C700272 “η s 176 % 141 %” |
| Seasonal space heating energy efficiency (ηs) | average climate, 55 °C application | 160 % | HP Keymark 012-C700272 “η s 210 % 160 %” |
| Seasonal space heating energy efficiency (ηs) | colder climate, 55 °C application | 141 % | HP Keymark 012-C700272 “η s 176 % 141 %” |
| Heating capacity | A-7/W35, max load | 11.42 kW | NIBE “Maximum capacity, heating, at A-7W35 kW 5.52 8.34 11.42 13.64” |
| Heating capacity | A-7/W35, partial load | 10.31 kW | NIBE “Heating -7 / 35 °C 4.72 / 1.72 / 2.74 7.23 / 2.73 / 2.65 10.31 / 3.72 / 2.77 12.03 / 4.56 / 2.64” |
| Heating capacity | A2/W35, partial load | 6.58 kW | NIBE “Capacity / power input / COP (kW/kW/-) at nominal flow 2 / 35 °C 3.20 / 0.72 / 4.44 3.67 / 0.85 / 4.32 6.58 / 1.41 / 4.66 7.38 / 1.59 / 4.63” |
| Heating capacity | A7/W35, partial load | 5.1 kW | NIBE “7 / 35 °C 3.15 / 0.61 / 5.16 3.67 / 0.70 / 5.24 5.10 / 0.92 / 5.55 5.10 / 0.92 / 5.55” |
| Heating capacity | A7/W45, partial load | 4.85 kW | NIBE “7 / 45 °C 2.97 / 0.76 / 3.90 3.35 / 0.85 / 3.94 4.85 / 1.18 / 4.12 4.85 / 1.18 / 4.12” |
| Operating range, cooling (outdoor air) | — | 45 °C | NIBE “Min./max. air temperature, cooling °C 15 / 43 15 / 43 15 / 45 15 / 45” |
| Operating range, cooling (outdoor air) | — | 15 °C | NIBE “Min./max. air temperature, cooling °C 15 / 43 15 / 43 15 / 45 15 / 45” |
| Operating range, heating (outdoor air) | — | 40 °C | NIBE “Min./max. air temperature, heating °C -25 / 38 -25 / 38 -25 / 40 -25 / 40” |
| Operating range, heating (outdoor air) | — | -25 °C | NIBE “Min./max. air temperature, heating °C -25 / 38 -25 / 38 -25 / 40 -25 / 40” |
| Power input (heating) | A-7/W35, partial load | 3.72 kW | NIBE “Heating -7 / 35 °C 4.72 / 1.72 / 2.74 7.23 / 2.73 / 2.65 10.31 / 3.72 / 2.77 12.03 / 4.56 / 2.64” |
| Power input (heating) | A2/W35, partial load | 1.41 kW | NIBE “Capacity / power input / COP (kW/kW/-) at nominal flow 2 / 35 °C 3.20 / 0.72 / 4.44 3.67 / 0.85 / 4.32 6.58 / 1.41 / 4.66 7.38 / 1.59 / 4.63” |
| Power input (heating) | A7/W35, partial load | 0.92 kW | NIBE “7 / 35 °C 3.15 / 0.61 / 5.16 3.67 / 0.70 / 5.24 5.10 / 0.92 / 5.55 5.10 / 0.92 / 5.55” |
| Power input (heating) | A7/W45, partial load | 1.18 kW | NIBE “7 / 45 °C 2.97 / 0.76 / 3.90 3.35 / 0.85 / 3.94 4.85 / 1.18 / 4.12 4.85 / 1.18 / 4.12” |
| Rated heat output (Prated) | average climate, 35 °C application | 11 kW | HP Keymark 012-C700272 “Prated 11.00 kW 11.00 kW” |
| Rated heat output (Prated) | average climate, 35 °C application | 11 kW | NIBE “Nominal heat output (Pdesignh) average climate kW 5.33 / 5.30 6.80 / 7.60 11.00 / 11.00 11.00 / 11.00” |
| Rated heat output (Prated) | colder climate, 35 °C application | 13 kW | HP Keymark 012-C700272 “Prated 13.00 kW 14.00 kW” |
| Rated heat output (Prated) | colder climate, 35 °C application | 13 kW | NIBE “Nominal heat output (Pdesignh) cold climate 35 °C / 55 °C kW 5.40 / 5.20 8.40 / 8.40 13.00 / 14.00 13.00 / 14.00” |
| Rated heat output (Prated) | warmer climate, 35 °C application | 13 kW | NIBE “Nominal heat output (Pdesignh) warm climate 35 °C / 55 °C kW 5.50 / 5.20 7.00 / 7.45 13.00 / 13.00 13.00 / 13.00” |
| Rated heat output (Prated) | average climate, 55 °C application | 11 kW | HP Keymark 012-C700272 “Prated 11.00 kW 11.00 kW” |
| Rated heat output (Prated) | average climate, 55 °C application | 11 kW | NIBE “Nominal heat output (Pdesignh) average climate kW 5.33 / 5.30 6.80 / 7.60 11.00 / 11.00 11.00 / 11.00” |
| Rated heat output (Prated) | colder climate, 55 °C application | 14 kW | HP Keymark 012-C700272 “Prated 13.00 kW 14.00 kW” |
| Rated heat output (Prated) | colder climate, 55 °C application | 14 kW | NIBE “Nominal heat output (Pdesignh) cold climate 35 °C / 55 °C kW 5.40 / 5.20 8.40 / 8.40 13.00 / 14.00 13.00 / 14.00” |
| Rated heat output (Prated) | warmer climate, 55 °C application | 13 kW | NIBE “Nominal heat output (Pdesignh) warm climate 35 °C / 55 °C kW 5.50 / 5.20 7.00 / 7.45 13.00 / 13.00 13.00 / 13.00” |
| Refrigerant charge | — | 1.15 kg | HP Keymark 012-C700272 “Mass of Refrigerant 1,150 kg” |
| Refrigerant charge | — | 1.15 kg | NIBE “Filling amount kg 0.8 0.8 1.15 1.15” |
| SCOP | average climate, 35 °C application | 5.34 | HP Keymark 012-C700272 “SCOP 5.34 4.08” |
| SCOP | average climate, 35 °C application | 5.33 | NIBE “SCOP average climate, 35 °C / 55 °C (Europe) 5.00 / 3.70 5.00 / 3.80 5.33 / 4.08 5.30 / 4.08” |
| SCOP | colder climate, 35 °C application | 4.48 | HP Keymark 012-C700272 “SCOP 4.48 3.59” |
| SCOP | colder climate, 35 °C application | 4.47 | NIBE “SCOP cold climate, 35 °C / 55 °C 4.10 / 3.20 4.20 / 3.40 4.47 / 3.59 4.60 / 3.69” |
| SCOP | warmer climate, 35 °C application | 5.98 | NIBE “SCOP warm climate, 35 °C / 55 °C 6.30 / 4.50 6.30 / 4.60 5.98 / 4.79 6.29 / 4.78” |
| SCOP | average climate, 55 °C application | 4.08 | HP Keymark 012-C700272 “SCOP 5.34 4.08” |
| SCOP | average climate, 55 °C application | 4.08 | NIBE “SCOP average climate, 35 °C / 55 °C (Europe) 5.00 / 3.70 5.00 / 3.80 5.33 / 4.08 5.30 / 4.08” |
| SCOP | colder climate, 55 °C application | 3.59 | HP Keymark 012-C700272 “SCOP 4.48 3.59” |
| SCOP | colder climate, 55 °C application | 3.59 | NIBE “SCOP cold climate, 35 °C / 55 °C 4.10 / 3.20 4.20 / 3.40 4.47 / 3.59 4.60 / 3.69” |
| SCOP | warmer climate, 55 °C application | 4.79 | NIBE “SCOP warm climate, 35 °C / 55 °C 6.30 / 4.50 6.30 / 4.60 5.98 / 4.79 6.29 / 4.78” |
| Bivalent temperature (Tbiv) | average climate, 35 °C application | -10 °C | HP Keymark 012-C700272 “Tbiv -10 °C -10 °C” |
| Bivalent temperature (Tbiv) | colder climate, 35 °C application | -12 °C | HP Keymark 012-C700272 “Tbiv -12 °C -11 °C” |
| Bivalent temperature (Tbiv) | average climate, 55 °C application | -10 °C | HP Keymark 012-C700272 “Tbiv -10 °C -10 °C” |
| Bivalent temperature (Tbiv) | colder climate, 55 °C application | -11 °C | HP Keymark 012-C700272 “Tbiv -12 °C -11 °C” |
| Operation limit temperature (TOL) | average climate, 35 °C application | -10 °C | HP Keymark 012-C700272 “TOL -10 °C -10 °C” |
| Operation limit temperature (TOL) | colder climate, 35 °C application | -22 °C | HP Keymark 012-C700272 “TOL -22 °C -22 °C” |
| Operation limit temperature (TOL) | average climate, 55 °C application | -10 °C | HP Keymark 012-C700272 “TOL -10 °C -10 °C” |
| Operation limit temperature (TOL) | colder climate, 55 °C application | -22 °C | HP Keymark 012-C700272 “TOL -22 °C -22 °C” |
Open questions
We have no manufacturer-stated maximum flow temperature for this unit (and the outdoor temperature down to which it is reached). If you know an official document that states it, you can submit its URL.
Question id
q:nibe-s2125-16-3x400v:max-flow-temperature·POST https://bedandbot.it/api/contributewith JSON{"question": "q:nibe-s2125-16-3x400v:max-flow-temperature", "source_url": "https://…"}. Submissions are stored as unverified. Nothing is published until our checks find the value in the cited source. Links to new domains are reviewed by a person first.
Values are copied from the cited source, with the quoted text they were read from. Seasonal values: EN 14825 (climate × application). Check the source before relying on a value.