PropertyConditionsValueSource
Seasonal space heating energy efficiency (ηs)average climate, 35 °C application200 %HP Keymark 011-1W0761
“η s 200 % 150 %”
Seasonal space heating energy efficiency (ηs)colder climate, 35 °C application181 %HP Keymark 011-1W0761
“η s 181 % 139 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 35 °C application271 %HP Keymark 011-1W0761
“η s 271 % 196 %”
Seasonal space heating energy efficiency (ηs)average climate, 55 °C application150 %HP Keymark 011-1W0761
“η s 200 % 150 %”
Seasonal space heating energy efficiency (ηs)colder climate, 55 °C application139 %HP Keymark 011-1W0761
“η s 181 % 139 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 55 °C application196 %HP Keymark 011-1W0761
“η s 271 % 196 %”
Rated heat output (Prated)average climate, 35 °C application11.91 kWHP Keymark 011-1W0761
“Prated 11.91 kW 11.65 kW”
Rated heat output (Prated)colder climate, 35 °C application12.57 kWHP Keymark 011-1W0761
“Prated 12.57 kW 12.98 kW”
Rated heat output (Prated)warmer climate, 35 °C application14.8 kWHP Keymark 011-1W0761
“Prated 14.80 kW 14.30 kW”
Rated heat output (Prated)average climate, 55 °C application11.65 kWHP Keymark 011-1W0761
“Prated 11.91 kW 11.65 kW”
Rated heat output (Prated)colder climate, 55 °C application12.98 kWHP Keymark 011-1W0761
“Prated 12.57 kW 12.98 kW”
Rated heat output (Prated)warmer climate, 55 °C application14.3 kWHP Keymark 011-1W0761
“Prated 14.80 kW 14.30 kW”
Refrigerant charge—1.3 kgHP Keymark 011-1W0761
“Mass of Refrigerant 1,300 kg”
SCOPaverage climate, 35 °C application5.08 HP Keymark 011-1W0761
“SCOP 5.08 3.83”
SCOPcolder climate, 35 °C application4.6 HP Keymark 011-1W0761
“SCOP 4.60 3.56”
SCOPwarmer climate, 35 °C application6.85 HP Keymark 011-1W0761
“SCOP 6.85 4.97”
SCOPaverage climate, 55 °C application3.83 HP Keymark 011-1W0761
“SCOP 5.08 3.83”
SCOPcolder climate, 55 °C application3.56 HP Keymark 011-1W0761
“SCOP 4.60 3.56”
SCOPwarmer climate, 55 °C application4.97 HP Keymark 011-1W0761
“SCOP 6.85 4.97”
Bivalent temperature (Tbiv)average climate, 35 °C application-9 °CHP Keymark 011-1W0761
“Tbiv -9 °C -9 °C”
Bivalent temperature (Tbiv)colder climate, 35 °C application-15 °CHP Keymark 011-1W0761
“Tbiv -15 °C -15 °C”
Bivalent temperature (Tbiv)warmer climate, 35 °C application2 °CHP Keymark 011-1W0761
“Tbiv 2 °C 2 °C”
Bivalent temperature (Tbiv)average climate, 55 °C application-9 °CHP Keymark 011-1W0761
“Tbiv -9 °C -9 °C”
Bivalent temperature (Tbiv)colder climate, 55 °C application-15 °CHP Keymark 011-1W0761
“Tbiv -15 °C -15 °C”
Bivalent temperature (Tbiv)warmer climate, 55 °C application2 °CHP Keymark 011-1W0761
“Tbiv 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 35 °C application-10 °CHP Keymark 011-1W0761
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 35 °C application-22 °CHP Keymark 011-1W0761
“TOL -22 °C -21 °C”
Operation limit temperature (TOL)warmer climate, 35 °C application2 °CHP Keymark 011-1W0761
“TOL 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 55 °C application-10 °CHP Keymark 011-1W0761
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 55 °C application-21 °CHP Keymark 011-1W0761
“TOL -22 °C -21 °C”
Operation limit temperature (TOL)warmer climate, 55 °C application2 °CHP Keymark 011-1W0761
“TOL 2 °C 2 °C”

Open questions

Values are copied from the cited source, with the quoted text they were read from. Seasonal values: EN 14825 (climate × application). Check the source before relying on a value.