PropertyConditionsValueSource
Seasonal space heating energy efficiency (ηs)average climate, 35 °C application186 %HP Keymark 011-1W0761
“η s 186 % 143 %”
Seasonal space heating energy efficiency (ηs)colder climate, 35 °C application168 %HP Keymark 011-1W0761
“η s 168 % 125 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 35 °C application244 %HP Keymark 011-1W0761
“η s 244 % 172 %”
Seasonal space heating energy efficiency (ηs)average climate, 55 °C application143 %HP Keymark 011-1W0761
“η s 186 % 143 %”
Seasonal space heating energy efficiency (ηs)colder climate, 55 °C application125 %HP Keymark 011-1W0761
“η s 168 % 125 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 55 °C application172 %HP Keymark 011-1W0761
“η s 244 % 172 %”
Rated heat output (Prated)average climate, 35 °C application12.69 kWHP Keymark 011-1W0761
“Prated 12.69 kW 12.00 kW”
Rated heat output (Prated)colder climate, 35 °C application12.73 kWHP Keymark 011-1W0761
“Prated 12.73 kW 12.17 kW”
Rated heat output (Prated)warmer climate, 35 °C application12.02 kWHP Keymark 011-1W0761
“Prated 12.02 kW 12.69 kW”
Rated heat output (Prated)average climate, 55 °C application12 kWHP Keymark 011-1W0761
“Prated 12.69 kW 12.00 kW”
Rated heat output (Prated)colder climate, 55 °C application12.17 kWHP Keymark 011-1W0761
“Prated 12.73 kW 12.17 kW”
Rated heat output (Prated)warmer climate, 55 °C application12.69 kWHP Keymark 011-1W0761
“Prated 12.02 kW 12.69 kW”
Refrigerant charge—1.3 kgHP Keymark 011-1W0761
“Mass of Refrigerant 1,300 kg”
SCOPaverage climate, 35 °C application4.73 HP Keymark 011-1W0761
“SCOP 4.73 3.65”
SCOPcolder climate, 35 °C application4.27 HP Keymark 011-1W0761
“SCOP 4.27 3.20”
SCOPwarmer climate, 35 °C application6.16 HP Keymark 011-1W0761
“SCOP 6.16 4.37”
SCOPaverage climate, 55 °C application3.65 HP Keymark 011-1W0761
“SCOP 4.73 3.65”
SCOPcolder climate, 55 °C application3.2 HP Keymark 011-1W0761
“SCOP 4.27 3.20”
SCOPwarmer climate, 55 °C application4.37 HP Keymark 011-1W0761
“SCOP 6.16 4.37”
Bivalent temperature (Tbiv)average climate, 35 °C application-7 °CHP Keymark 011-1W0761
“Tbiv -7 °C -7 °C”
Bivalent temperature (Tbiv)colder climate, 35 °C application-15 °CHP Keymark 011-1W0761
“Tbiv -15 °C -15 °C”
Bivalent temperature (Tbiv)warmer climate, 35 °C application2 °CHP Keymark 011-1W0761
“Tbiv 2 °C 2 °C”
Bivalent temperature (Tbiv)average climate, 55 °C application-7 °CHP Keymark 011-1W0761
“Tbiv -7 °C -7 °C”
Bivalent temperature (Tbiv)colder climate, 55 °C application-15 °CHP Keymark 011-1W0761
“Tbiv -15 °C -15 °C”
Bivalent temperature (Tbiv)warmer climate, 55 °C application2 °CHP Keymark 011-1W0761
“Tbiv 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 35 °C application-10 °CHP Keymark 011-1W0761
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 35 °C application-20 °CHP Keymark 011-1W0761
“TOL -20 °C -20 °C”
Operation limit temperature (TOL)warmer climate, 35 °C application2 °CHP Keymark 011-1W0761
“TOL 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 55 °C application-10 °CHP Keymark 011-1W0761
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 55 °C application-20 °CHP Keymark 011-1W0761
“TOL -20 °C -20 °C”
Operation limit temperature (TOL)warmer climate, 55 °C application2 °CHP Keymark 011-1W0761
“TOL 2 °C 2 °C”

Open questions