Vaillant VWL 65/6 A 230V S2

air-to-water monobloc · refrigerant R290 · 1x230V 50Hz · family aroTHERM plus

Machine-readable: https://bedandbot.it/p/vaillant-vwl-65-6-a-230v-s2.json

PropertyConditionsValueSource
Seasonal space heating energy efficiency (ηs)average climate, 35 °C application185 %HP Keymark 011-1W0760
“η s 185 % 130 %”
Seasonal space heating energy efficiency (ηs)colder climate, 35 °C application160 %HP Keymark 011-1W0760
“η s 160 % 116 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 35 °C application226 %HP Keymark 011-1W0760
“η s 226 % 161 %”
Seasonal space heating energy efficiency (ηs)average climate, 55 °C application130 %HP Keymark 011-1W0760
“η s 185 % 130 %”
Seasonal space heating energy efficiency (ηs)colder climate, 55 °C application116 %HP Keymark 011-1W0760
“η s 160 % 116 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 55 °C application161 %HP Keymark 011-1W0760
“η s 226 % 161 %”
Rated heat output (Prated)average climate, 35 °C application5.75 kWHP Keymark 011-1W0760
“Prated 5.75 kW 4.49 kW”
Rated heat output (Prated)colder climate, 35 °C application4.25 kWHP Keymark 011-1W0760
“Prated 4.25 kW 3.92 kW”
Rated heat output (Prated)warmer climate, 35 °C application5.71 kWHP Keymark 011-1W0760
“Prated 5.71 kW 6.10 kW”
Rated heat output (Prated)average climate, 55 °C application4.49 kWHP Keymark 011-1W0760
“Prated 5.75 kW 4.49 kW”
Rated heat output (Prated)colder climate, 55 °C application3.92 kWHP Keymark 011-1W0760
“Prated 4.25 kW 3.92 kW”
Rated heat output (Prated)warmer climate, 55 °C application6.1 kWHP Keymark 011-1W0760
“Prated 5.71 kW 6.10 kW”
Refrigerant charge—0.9 kgHP Keymark 011-1W0760
“Mass of Refrigerant 0,900 kg”
SCOPaverage climate, 35 °C application4.71 HP Keymark 011-1W0760
“SCOP 4.71 3.32”
SCOPcolder climate, 35 °C application4.08 HP Keymark 011-1W0760
“SCOP 4.08 2.98”
SCOPwarmer climate, 35 °C application5.71 HP Keymark 011-1W0760
“SCOP 5.71 4.09”
SCOPaverage climate, 55 °C application3.32 HP Keymark 011-1W0760
“SCOP 4.71 3.32”
SCOPcolder climate, 55 °C application2.98 HP Keymark 011-1W0760
“SCOP 4.08 2.98”
SCOPwarmer climate, 55 °C application4.09 HP Keymark 011-1W0760
“SCOP 5.71 4.09”
Bivalent temperature (Tbiv)average climate, 35 °C application-10 °CHP Keymark 011-1W0760
“Tbiv -10 °C -10 °C”
Bivalent temperature (Tbiv)colder climate, 35 °C application-20 °CHP Keymark 011-1W0760
“Tbiv -20 °C -20 °C”
Bivalent temperature (Tbiv)warmer climate, 35 °C application2 °CHP Keymark 011-1W0760
“Tbiv 2 °C 2 °C”
Bivalent temperature (Tbiv)average climate, 55 °C application-10 °CHP Keymark 011-1W0760
“Tbiv -10 °C -10 °C”
Bivalent temperature (Tbiv)colder climate, 55 °C application-20 °CHP Keymark 011-1W0760
“Tbiv -20 °C -20 °C”
Bivalent temperature (Tbiv)warmer climate, 55 °C application2 °CHP Keymark 011-1W0760
“Tbiv 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 35 °C application-10 °CHP Keymark 011-1W0760
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 35 °C application-20 °CHP Keymark 011-1W0760
“TOL -20 °C -20 °C”
Operation limit temperature (TOL)warmer climate, 35 °C application2 °CHP Keymark 011-1W0760
“TOL 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 55 °C application-10 °CHP Keymark 011-1W0760
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 55 °C application-20 °CHP Keymark 011-1W0760
“TOL -20 °C -20 °C”
Operation limit temperature (TOL)warmer climate, 55 °C application2 °CHP Keymark 011-1W0760
“TOL 2 °C 2 °C”

Open questions

Values are copied from the cited source, with the quoted text they were read from. Seasonal values: EN 14825 (climate × application). Check the source before relying on a value.