Vaillant VWL 85/6 A 230V S3

air-to-water monobloc · refrigerant R290 · 1x230V 50Hz · family aroTHERM plus

Machine-readable: https://bedandbot.it/p/vaillant-vwl-85-6-a-230v-s3.json

PropertyConditionsValueSource
Seasonal space heating energy efficiency (ηs)average climate, 35 °C application187 %HP Keymark 011-1W0760
“η s 187 % 135 %”
Seasonal space heating energy efficiency (ηs)colder climate, 35 °C application159 %HP Keymark 011-1W0760
“η s 159 % 119 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 35 °C application228 %HP Keymark 011-1W0760
“η s 228 % 162 %”
Seasonal space heating energy efficiency (ηs)average climate, 55 °C application135 %HP Keymark 011-1W0760
“η s 187 % 135 %”
Seasonal space heating energy efficiency (ηs)colder climate, 55 °C application119 %HP Keymark 011-1W0760
“η s 159 % 119 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 55 °C application162 %HP Keymark 011-1W0760
“η s 228 % 162 %”
Rated heat output (Prated)average climate, 35 °C application7.21 kWHP Keymark 011-1W0760
“Prated 7.21 kW 6.39 kW”
Rated heat output (Prated)colder climate, 35 °C application6.03 kWHP Keymark 011-1W0760
“Prated 6.03 kW 5.59 kW”
Rated heat output (Prated)warmer climate, 35 °C application6.87 kWHP Keymark 011-1W0760
“Prated 6.87 kW 7.06 kW”
Rated heat output (Prated)average climate, 55 °C application6.39 kWHP Keymark 011-1W0760
“Prated 7.21 kW 6.39 kW”
Rated heat output (Prated)colder climate, 55 °C application5.59 kWHP Keymark 011-1W0760
“Prated 6.03 kW 5.59 kW”
Rated heat output (Prated)warmer climate, 55 °C application7.06 kWHP Keymark 011-1W0760
“Prated 6.87 kW 7.06 kW”
Refrigerant charge—0.9 kgHP Keymark 011-1W0760
“Mass of Refrigerant 0,900 kg”
SCOPaverage climate, 35 °C application4.75 HP Keymark 011-1W0760
“SCOP 4.75 3.44”
SCOPcolder climate, 35 °C application4.05 HP Keymark 011-1W0760
“SCOP 4.05 3.06”
SCOPwarmer climate, 35 °C application5.78 HP Keymark 011-1W0760
“SCOP 5.78 4.13”
SCOPaverage climate, 55 °C application3.44 HP Keymark 011-1W0760
“SCOP 4.75 3.44”
SCOPcolder climate, 55 °C application3.06 HP Keymark 011-1W0760
“SCOP 4.05 3.06”
SCOPwarmer climate, 55 °C application4.13 HP Keymark 011-1W0760
“SCOP 5.78 4.13”
Bivalent temperature (Tbiv)average climate, 35 °C application-7 °CHP Keymark 011-1W0760
“Tbiv -7 °C -7 °C”
Bivalent temperature (Tbiv)colder climate, 35 °C application-15 °CHP Keymark 011-1W0760
“Tbiv -15 °C -15 °C”
Bivalent temperature (Tbiv)warmer climate, 35 °C application2 °CHP Keymark 011-1W0760
“Tbiv 2 °C 2 °C”
Bivalent temperature (Tbiv)average climate, 55 °C application-7 °CHP Keymark 011-1W0760
“Tbiv -7 °C -7 °C”
Bivalent temperature (Tbiv)colder climate, 55 °C application-15 °CHP Keymark 011-1W0760
“Tbiv -15 °C -15 °C”
Bivalent temperature (Tbiv)warmer climate, 55 °C application2 °CHP Keymark 011-1W0760
“Tbiv 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 35 °C application-10 °CHP Keymark 011-1W0760
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 35 °C application-20 °CHP Keymark 011-1W0760
“TOL -20 °C -20 °C”
Operation limit temperature (TOL)warmer climate, 35 °C application2 °CHP Keymark 011-1W0760
“TOL 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 55 °C application-10 °CHP Keymark 011-1W0760
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 55 °C application-20 °CHP Keymark 011-1W0760
“TOL -20 °C -20 °C”
Operation limit temperature (TOL)warmer climate, 55 °C application2 °CHP Keymark 011-1W0760
“TOL 2 °C 2 °C”

Open questions