PropertyConditionsValueSource
Seasonal space heating energy efficiency (ηs)average climate, 35 °C application180 %HP Keymark 011-1W0590
“η s 180 % 141 %”
Seasonal space heating energy efficiency (ηs)colder climate, 35 °C application149 %HP Keymark 011-1W0590
“η s 149 % 119 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 35 °C application220 %HP Keymark 011-1W0590
“η s 220 % 153 %”
Seasonal space heating energy efficiency (ηs)average climate, 55 °C application141 %HP Keymark 011-1W0590
“η s 180 % 141 %”
Seasonal space heating energy efficiency (ηs)colder climate, 55 °C application119 %HP Keymark 011-1W0590
“η s 149 % 119 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 55 °C application153 %HP Keymark 011-1W0590
“η s 220 % 153 %”
Rated heat output (Prated)average climate, 35 °C application5.46 kWHP Keymark 011-1W0590
“Prated 5.46 kW 5.14 kW”
Rated heat output (Prated)colder climate, 35 °C application6.51 kWHP Keymark 011-1W0590
“Prated 6.51 kW 6.71 kW”
Rated heat output (Prated)warmer climate, 35 °C application2.77 kWHP Keymark 011-1W0590
“Prated 2.77 kW 2.38 kW”
Rated heat output (Prated)average climate, 55 °C application5.14 kWHP Keymark 011-1W0590
“Prated 5.46 kW 5.14 kW”
Rated heat output (Prated)colder climate, 55 °C application6.71 kWHP Keymark 011-1W0590
“Prated 6.51 kW 6.71 kW”
Rated heat output (Prated)warmer climate, 55 °C application2.38 kWHP Keymark 011-1W0590
“Prated 2.77 kW 2.38 kW”
Refrigerant charge—1.2 kgHP Keymark 011-1W0590
“Mass of Refrigerant 1,200 kg”
SCOPaverage climate, 35 °C application4.58 HP Keymark 011-1W0590
“SCOP 4.58 3.61”
SCOPcolder climate, 35 °C application3.8 HP Keymark 011-1W0590
“SCOP 3.80 3.04”
SCOPwarmer climate, 35 °C application5.58 HP Keymark 011-1W0590
“SCOP 5.58 3.89”
SCOPaverage climate, 55 °C application3.61 HP Keymark 011-1W0590
“SCOP 4.58 3.61”
SCOPcolder climate, 55 °C application3.04 HP Keymark 011-1W0590
“SCOP 3.80 3.04”
SCOPwarmer climate, 55 °C application3.89 HP Keymark 011-1W0590
“SCOP 5.58 3.89”
Bivalent temperature (Tbiv)average climate, 35 °C application-7 °CHP Keymark 011-1W0590
“Tbiv -7 °C -7 °C”
Bivalent temperature (Tbiv)colder climate, 35 °C application-10 °CHP Keymark 011-1W0590
“Tbiv -10 °C -9 °C”
Bivalent temperature (Tbiv)warmer climate, 35 °C application2 °CHP Keymark 011-1W0590
“Tbiv 2 °C 2 °C”
Bivalent temperature (Tbiv)average climate, 55 °C application-7 °CHP Keymark 011-1W0590
“Tbiv -7 °C -7 °C”
Bivalent temperature (Tbiv)colder climate, 55 °C application-9 °CHP Keymark 011-1W0590
“Tbiv -10 °C -9 °C”
Bivalent temperature (Tbiv)warmer climate, 55 °C application2 °CHP Keymark 011-1W0590
“Tbiv 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 35 °C application-10 °CHP Keymark 011-1W0590
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 35 °C application-20 °CHP Keymark 011-1W0590
“TOL -20 °C -20 °C”
Operation limit temperature (TOL)warmer climate, 35 °C application2 °CHP Keymark 011-1W0590
“TOL 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 55 °C application-10 °CHP Keymark 011-1W0590
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 55 °C application-20 °CHP Keymark 011-1W0590
“TOL -20 °C -20 °C”
Operation limit temperature (TOL)warmer climate, 55 °C application2 °CHP Keymark 011-1W0590
“TOL 2 °C 2 °C”

Open questions