Viessmann IDU-A Modular AWMIW.A1.19-V051 / ODU 150-A AWMOF-151.A1.04-230-V001

air-to-water monobloc · refrigerant R290 · 1x230V 50Hz · family Vitocal 250-A

Machine-readable: https://bedandbot.it/p/viessmann-idu-a-modular-awmiw-a1-19-v051-odu-150-a-awmof-151-a1-04-230-v001.json

PropertyConditionsValueSource
Seasonal space heating energy efficiency (ηs)average climate, 35 °C application176 %HP Keymark 011-1W0590
“η s 176 % 127 %”
Seasonal space heating energy efficiency (ηs)colder climate, 35 °C application148 %HP Keymark 011-1W0590
“η s 148 % 122 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 35 °C application216 %HP Keymark 011-1W0590
“η s 216 % 146 %”
Seasonal space heating energy efficiency (ηs)average climate, 55 °C application127 %HP Keymark 011-1W0590
“η s 176 % 127 %”
Seasonal space heating energy efficiency (ηs)colder climate, 55 °C application122 %HP Keymark 011-1W0590
“η s 148 % 122 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 55 °C application146 %HP Keymark 011-1W0590
“η s 216 % 146 %”
Rated heat output (Prated)average climate, 35 °C application4.08 kWHP Keymark 011-1W0590
“Prated 4.08 kW 3.77 kW”
Rated heat output (Prated)colder climate, 35 °C application5.62 kWHP Keymark 011-1W0590
“Prated 5.62 kW 5.36 kW”
Rated heat output (Prated)warmer climate, 35 °C application2.35 kWHP Keymark 011-1W0590
“Prated 2.35 kW 1.90 kW”
Rated heat output (Prated)average climate, 55 °C application3.77 kWHP Keymark 011-1W0590
“Prated 4.08 kW 3.77 kW”
Rated heat output (Prated)colder climate, 55 °C application5.36 kWHP Keymark 011-1W0590
“Prated 5.62 kW 5.36 kW”
Rated heat output (Prated)warmer climate, 55 °C application1.9 kWHP Keymark 011-1W0590
“Prated 2.35 kW 1.90 kW”
Refrigerant charge—1.2 kgHP Keymark 011-1W0590
“Mass of Refrigerant 1,200 kg”
SCOPaverage climate, 35 °C application4.48 HP Keymark 011-1W0590
“SCOP 4.48 3.25”
SCOPcolder climate, 35 °C application3.78 HP Keymark 011-1W0590
“SCOP 3.78 3.13”
SCOPwarmer climate, 35 °C application5.47 HP Keymark 011-1W0590
“SCOP 5.47 3.73”
SCOPaverage climate, 55 °C application3.25 HP Keymark 011-1W0590
“SCOP 4.48 3.25”
SCOPcolder climate, 55 °C application3.13 HP Keymark 011-1W0590
“SCOP 3.78 3.13”
SCOPwarmer climate, 55 °C application3.73 HP Keymark 011-1W0590
“SCOP 5.47 3.73”
Bivalent temperature (Tbiv)average climate, 35 °C application-8 °CHP Keymark 011-1W0590
“Tbiv -8 °C -8 °C”
Bivalent temperature (Tbiv)colder climate, 35 °C application-9 °CHP Keymark 011-1W0590
“Tbiv -9 °C -9 °C”
Bivalent temperature (Tbiv)warmer climate, 35 °C application2 °CHP Keymark 011-1W0590
“Tbiv 2 °C 2 °C”
Bivalent temperature (Tbiv)average climate, 55 °C application-8 °CHP Keymark 011-1W0590
“Tbiv -8 °C -8 °C”
Bivalent temperature (Tbiv)colder climate, 55 °C application-9 °CHP Keymark 011-1W0590
“Tbiv -9 °C -9 °C”
Bivalent temperature (Tbiv)warmer climate, 55 °C application2 °CHP Keymark 011-1W0590
“Tbiv 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 35 °C application-10 °CHP Keymark 011-1W0590
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 35 °C application-20 °CHP Keymark 011-1W0590
“TOL -20 °C -20 °C”
Operation limit temperature (TOL)warmer climate, 35 °C application2 °CHP Keymark 011-1W0590
“TOL 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 55 °C application-10 °CHP Keymark 011-1W0590
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 55 °C application-20 °CHP Keymark 011-1W0590
“TOL -20 °C -20 °C”
Operation limit temperature (TOL)warmer climate, 55 °C application2 °CHP Keymark 011-1W0590
“TOL 2 °C 2 °C”

Open questions