Viessmann IDU-A Modular AWMIW.A1.19-V051 / ODU 150-A AWMOF-151.A1.16-400-V002

air-to-water monobloc · refrigerant R290 · 3x400V 50Hz · family Vitocal 250-A

Machine-readable: https://bedandbot.it/p/viessmann-idu-a-modular-awmiw-a1-19-v051-odu-150-a-awmof-151-a1-16-400-v002.json

PropertyConditionsValueSource
Seasonal space heating energy efficiency (ηs)average climate, 35 °C application188 %HP Keymark 011-1W0465
“η s 188 % 150 %”
Seasonal space heating energy efficiency (ηs)colder climate, 35 °C application141 %HP Keymark 011-1W0465
“η s 141 % 117 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 35 °C application239 %HP Keymark 011-1W0465
“η s 239 % 175 %”
Seasonal space heating energy efficiency (ηs)average climate, 55 °C application150 %HP Keymark 011-1W0465
“η s 188 % 150 %”
Seasonal space heating energy efficiency (ηs)colder climate, 55 °C application117 %HP Keymark 011-1W0465
“η s 141 % 117 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 55 °C application175 %HP Keymark 011-1W0465
“η s 239 % 175 %”
Rated heat output (Prated)average climate, 35 °C application13.67 kWHP Keymark 011-1W0465
“Prated 13.67 kW 13.37 kW”
Rated heat output (Prated)colder climate, 35 °C application11.83 kWHP Keymark 011-1W0465
“Prated 11.83 kW 11.17 kW”
Rated heat output (Prated)warmer climate, 35 °C application7.54 kWHP Keymark 011-1W0465
“Prated 7.54 kW 7.56 kW”
Rated heat output (Prated)average climate, 55 °C application13.37 kWHP Keymark 011-1W0465
“Prated 13.67 kW 13.37 kW”
Rated heat output (Prated)colder climate, 55 °C application11.17 kWHP Keymark 011-1W0465
“Prated 11.83 kW 11.17 kW”
Rated heat output (Prated)warmer climate, 55 °C application7.56 kWHP Keymark 011-1W0465
“Prated 7.54 kW 7.56 kW”
Refrigerant charge—2 kgHP Keymark 011-1W0465
“Mass of Refrigerant 2,000 kg”
SCOPaverage climate, 35 °C application4.78 HP Keymark 011-1W0465
“SCOP 4.78 3.82”
SCOPcolder climate, 35 °C application3.61 HP Keymark 011-1W0465
“SCOP 3.61 2.99”
SCOPwarmer climate, 35 °C application6.06 HP Keymark 011-1W0465
“SCOP 6.06 4.46”
SCOPaverage climate, 55 °C application3.82 HP Keymark 011-1W0465
“SCOP 4.78 3.82”
SCOPcolder climate, 55 °C application2.99 HP Keymark 011-1W0465
“SCOP 3.61 2.99”
SCOPwarmer climate, 55 °C application4.46 HP Keymark 011-1W0465
“SCOP 6.06 4.46”
Bivalent temperature (Tbiv)average climate, 35 °C application-7 °CHP Keymark 011-1W0465
“Tbiv -7 °C -7 °C”
Bivalent temperature (Tbiv)colder climate, 35 °C application-15 °CHP Keymark 011-1W0465
“Tbiv -15 °C -15 °C”
Bivalent temperature (Tbiv)warmer climate, 35 °C application2 °CHP Keymark 011-1W0465
“Tbiv 2 °C 2 °C”
Bivalent temperature (Tbiv)average climate, 55 °C application-7 °CHP Keymark 011-1W0465
“Tbiv -7 °C -7 °C”
Bivalent temperature (Tbiv)colder climate, 55 °C application-15 °CHP Keymark 011-1W0465
“Tbiv -15 °C -15 °C”
Bivalent temperature (Tbiv)warmer climate, 55 °C application2 °CHP Keymark 011-1W0465
“Tbiv 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 35 °C application-10 °CHP Keymark 011-1W0465
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 35 °C application-20 °CHP Keymark 011-1W0465
“TOL -20 °C -20 °C”
Operation limit temperature (TOL)warmer climate, 35 °C application2 °CHP Keymark 011-1W0465
“TOL 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 55 °C application-10 °CHP Keymark 011-1W0465
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 55 °C application-20 °CHP Keymark 011-1W0465
“TOL -20 °C -20 °C”
Operation limit temperature (TOL)warmer climate, 55 °C application2 °CHP Keymark 011-1W0465
“TOL 2 °C 2 °C”

Open questions