Viessmann Vitocal 250-A AWO-M-E-AC-AF 251.A06 SP

air-to-water monobloc · refrigerant R290 · 1x230V 50Hz · family Vitocal 250-A

Machine-readable: https://bedandbot.it/p/viessmann-vitocal-250-a-awo-m-e-ac-af-251-a06-sp.json

PropertyConditionsValueSource
Seasonal space heating energy efficiency (ηs)average climate, 35 °C application183 %HP Keymark 011-1W0590
“η s 183 % 141 %”
Seasonal space heating energy efficiency (ηs)colder climate, 35 °C application152 %HP Keymark 011-1W0590
“η s 152 % 120 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 35 °C application226 %HP Keymark 011-1W0590
“η s 226 % 154 %”
Seasonal space heating energy efficiency (ηs)average climate, 55 °C application141 %HP Keymark 011-1W0590
“η s 183 % 141 %”
Seasonal space heating energy efficiency (ηs)colder climate, 55 °C application120 %HP Keymark 011-1W0590
“η s 152 % 120 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 55 °C application154 %HP Keymark 011-1W0590
“η s 226 % 154 %”
Rated heat output (Prated)average climate, 35 °C application5.41 kWHP Keymark 011-1W0590
“Prated 5.41 kW 5.11 kW”
Rated heat output (Prated)colder climate, 35 °C application6.47 kWHP Keymark 011-1W0590
“Prated 6.47 kW 6.67 kW”
Rated heat output (Prated)warmer climate, 35 °C application2.75 kWHP Keymark 011-1W0590
“Prated 2.75 kW 2.37 kW”
Rated heat output (Prated)average climate, 55 °C application5.11 kWHP Keymark 011-1W0590
“Prated 5.41 kW 5.11 kW”
Rated heat output (Prated)colder climate, 55 °C application6.67 kWHP Keymark 011-1W0590
“Prated 6.47 kW 6.67 kW”
Rated heat output (Prated)warmer climate, 55 °C application2.37 kWHP Keymark 011-1W0590
“Prated 2.75 kW 2.37 kW”
Refrigerant charge—1.2 kgHP Keymark 011-1W0590
“Mass of Refrigerant 1,200 kg”
SCOPaverage climate, 35 °C application4.71 HP Keymark 011-1W0590
“SCOP 4.71 3.65”
SCOPcolder climate, 35 °C application3.88 HP Keymark 011-1W0590
“SCOP 3.88 3.08”
SCOPwarmer climate, 35 °C application5.72 HP Keymark 011-1W0590
“SCOP 5.72 3.93”
SCOPaverage climate, 55 °C application3.65 HP Keymark 011-1W0590
“SCOP 4.71 3.65”
SCOPcolder climate, 55 °C application3.08 HP Keymark 011-1W0590
“SCOP 3.88 3.08”
SCOPwarmer climate, 55 °C application3.93 HP Keymark 011-1W0590
“SCOP 5.72 3.93”
Bivalent temperature (Tbiv)average climate, 35 °C application-7 °CHP Keymark 011-1W0590
“Tbiv -7 °C -7 °C”
Bivalent temperature (Tbiv)colder climate, 35 °C application-10 °CHP Keymark 011-1W0590
“Tbiv -10 °C -9 °C”
Bivalent temperature (Tbiv)warmer climate, 35 °C application2 °CHP Keymark 011-1W0590
“Tbiv 2 °C 2 °C”
Bivalent temperature (Tbiv)average climate, 55 °C application-7 °CHP Keymark 011-1W0590
“Tbiv -7 °C -7 °C”
Bivalent temperature (Tbiv)colder climate, 55 °C application-9 °CHP Keymark 011-1W0590
“Tbiv -10 °C -9 °C”
Bivalent temperature (Tbiv)warmer climate, 55 °C application2 °CHP Keymark 011-1W0590
“Tbiv 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 35 °C application-10 °CHP Keymark 011-1W0590
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 35 °C application-20 °CHP Keymark 011-1W0590
“TOL -20 °C -20 °C”
Operation limit temperature (TOL)warmer climate, 35 °C application2 °CHP Keymark 011-1W0590
“TOL 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 55 °C application-10 °CHP Keymark 011-1W0590
“TOL -10 °C -10 °C”
Operation limit temperature (TOL)colder climate, 55 °C application-20 °CHP Keymark 011-1W0590
“TOL -20 °C -20 °C”
Operation limit temperature (TOL)warmer climate, 55 °C application2 °CHP Keymark 011-1W0590
“TOL 2 °C 2 °C”

Open questions