Wolf CHA-07/400V

air-to-water monobloc · refrigerant R290 · 3x400V 50Hz · family CHA-Monoblock

Machine-readable: https://bedandbot.it/p/wolf-cha-07-400v.json

PropertyConditionsValueSource
Seasonal space heating energy efficiency (ηs)average climate, 35 °C application194 %HP Keymark 011-1W380
“η s 194 % 148 %”
Seasonal space heating energy efficiency (ηs)colder climate, 35 °C application174 %HP Keymark 011-1W380
“η s 174 % 127 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 35 °C application249 %HP Keymark 011-1W380
“η s 249 % 179 %”
Seasonal space heating energy efficiency (ηs)average climate, 55 °C application148 %HP Keymark 011-1W380
“η s 194 % 148 %”
Seasonal space heating energy efficiency (ηs)colder climate, 55 °C application127 %HP Keymark 011-1W380
“η s 174 % 127 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 55 °C application179 %HP Keymark 011-1W380
“η s 249 % 179 %”
Rated heat output (Prated)average climate, 35 °C application5.59 kWHP Keymark 011-1W380
“Prated 5.59 kW 5.93 kW”
Rated heat output (Prated)colder climate, 35 °C application6.16 kWHP Keymark 011-1W380
“Prated 6.16 kW 5.57 kW”
Rated heat output (Prated)warmer climate, 35 °C application5.7 kWHP Keymark 011-1W380
“Prated 5.70 kW 5.89 kW”
Rated heat output (Prated)average climate, 55 °C application5.93 kWHP Keymark 011-1W380
“Prated 5.59 kW 5.93 kW”
Rated heat output (Prated)colder climate, 55 °C application5.57 kWHP Keymark 011-1W380
“Prated 6.16 kW 5.57 kW”
Rated heat output (Prated)warmer climate, 55 °C application5.89 kWHP Keymark 011-1W380
“Prated 5.70 kW 5.89 kW”
Refrigerant charge—3.1 kgHP Keymark 011-1W380
“Mass of Refrigerant 3,100 kg”
SCOPaverage climate, 35 °C application4.92 HP Keymark 011-1W380
“SCOP 4.92 3.77”
SCOPcolder climate, 35 °C application4.43 HP Keymark 011-1W380
“SCOP 4.43 3.26”
SCOPwarmer climate, 35 °C application6.3 HP Keymark 011-1W380
“SCOP 6.30 4.54”
SCOPaverage climate, 55 °C application3.77 HP Keymark 011-1W380
“SCOP 4.92 3.77”
SCOPcolder climate, 55 °C application3.26 HP Keymark 011-1W380
“SCOP 4.43 3.26”
SCOPwarmer climate, 55 °C application4.54 HP Keymark 011-1W380
“SCOP 6.30 4.54”
Bivalent temperature (Tbiv)average climate, 35 °C application-10 °CHP Keymark 011-1W380
“Tbiv -10 °C -10 °C”
Bivalent temperature (Tbiv)colder climate, 35 °C application-17 °CHP Keymark 011-1W380
“Tbiv -17 °C -17 °C”
Bivalent temperature (Tbiv)warmer climate, 35 °C application2 °CHP Keymark 011-1W380
“Tbiv 2 °C 2 °C”
Bivalent temperature (Tbiv)average climate, 55 °C application-10 °CHP Keymark 011-1W380
“Tbiv -10 °C -10 °C”
Bivalent temperature (Tbiv)colder climate, 55 °C application-17 °CHP Keymark 011-1W380
“Tbiv -17 °C -17 °C”
Bivalent temperature (Tbiv)warmer climate, 55 °C application2 °CHP Keymark 011-1W380
“Tbiv 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 35 °C application-22 °CHP Keymark 011-1W380
“TOL -22 °C -22 °C”
Operation limit temperature (TOL)colder climate, 35 °C application-22 °CHP Keymark 011-1W380
“TOL -22 °C -22 °C”
Operation limit temperature (TOL)warmer climate, 35 °C application-22 °CHP Keymark 011-1W380
“TOL -22 °C -22 °C”
Operation limit temperature (TOL)average climate, 55 °C application-22 °CHP Keymark 011-1W380
“TOL -22 °C -22 °C”
Operation limit temperature (TOL)colder climate, 55 °C application-22 °CHP Keymark 011-1W380
“TOL -22 °C -22 °C”
Operation limit temperature (TOL)warmer climate, 55 °C application-22 °CHP Keymark 011-1W380
“TOL -22 °C -22 °C”

Open questions

Values are copied from the cited source, with the quoted text they were read from. Seasonal values: EN 14825 (climate × application). Check the source before relying on a value.