 "values": [
  {
   "id": "bb:value:27721",
   "property": "eta_s",
   "label": "Seasonal space heating energy efficiency (ηs)",
   "value": 215.0,
   "unit": "%",
   "conditions": {
    "application_c": 35,
    "climate": "average"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "η s 215 % 154 %",
    "location": "model CHA-16/20-400V-M2 CS-C2, average climate, EN 14825, 35 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27711",
   "property": "eta_s",
   "label": "Seasonal space heating energy efficiency (ηs)",
   "value": 266.0,
   "unit": "%",
   "conditions": {
    "application_c": 35,
    "climate": "warmer"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "η s 266 % 185 %",
    "location": "model CHA-16/20-400V-M2 CS-C2, warmer climate, EN 14825, 35 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27722",
   "property": "eta_s",
   "label": "Seasonal space heating energy efficiency (ηs)",
   "value": 154.0,
   "unit": "%",
   "conditions": {
    "application_c": 55,
    "climate": "average"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "η s 215 % 154 %",
    "location": "model CHA-16/20-400V-M2 CS-C2, average climate, EN 14825, 55 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27712",
   "property": "eta_s",
   "label": "Seasonal space heating energy efficiency (ηs)",
   "value": 185.0,
   "unit": "%",
   "conditions": {
    "application_c": 55,
    "climate": "warmer"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "η s 266 % 185 %",
    "location": "model CHA-16/20-400V-M2 CS-C2, warmer climate, EN 14825, 55 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27723",
   "property": "prated",
   "label": "Rated heat output (Prated)",
   "value": 13.52,
   "unit": "kW",
   "conditions": {
    "application_c": 35,
    "climate": "average"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "Prated 13.52 kW 14.55 kW",
    "location": "model CHA-16/20-400V-M2 CS-C2, average climate, EN 14825, 35 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27713",
   "property": "prated",
   "label": "Rated heat output (Prated)",
   "value": 15.17,
   "unit": "kW",
   "conditions": {
    "application_c": 35,
    "climate": "warmer"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "Prated 15.17 kW 15.98 kW",
    "location": "model CHA-16/20-400V-M2 CS-C2, warmer climate, EN 14825, 35 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27724",
   "property": "prated",
   "label": "Rated heat output (Prated)",
   "value": 14.55,
   "unit": "kW",
   "conditions": {
    "application_c": 55,
    "climate": "average"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "Prated 13.52 kW 14.55 kW",
    "location": "model CHA-16/20-400V-M2 CS-C2, average climate, EN 14825, 55 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27714",
   "property": "prated",
   "label": "Rated heat output (Prated)",
   "value": 15.98,
   "unit": "kW",
   "conditions": {
    "application_c": 55,
    "climate": "warmer"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "Prated 15.17 kW 15.98 kW",
    "location": "model CHA-16/20-400V-M2 CS-C2, warmer climate, EN 14825, 55 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27731",
   "property": "refrigerant_charge",
   "label": "Refrigerant charge",
   "value": 3.8,
   "unit": "kg",
   "conditions": {},
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "Mass of Refrigerant 3,800 kg",
    "location": "subtype CHA-Monoblock 16, general data"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27725",
   "property": "scop",
   "label": "SCOP",
   "value": 5.46,
   "unit": "-",
   "conditions": {
    "application_c": 35,
    "climate": "average"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "SCOP 5.46 3.92",
    "location": "model CHA-16/20-400V-M2 CS-C2, average climate, EN 14825, 35 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27715",
   "property": "scop",
   "label": "SCOP",
   "value": 6.72,
   "unit": "-",
   "conditions": {
    "application_c": 35,
    "climate": "warmer"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "SCOP 6.72 4.71",
    "location": "model CHA-16/20-400V-M2 CS-C2, warmer climate, EN 14825, 35 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27726",
   "property": "scop",
   "label": "SCOP",
   "value": 3.92,
   "unit": "-",
   "conditions": {
    "application_c": 55,
    "climate": "average"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "SCOP 5.46 3.92",
    "location": "model CHA-16/20-400V-M2 CS-C2, average climate, EN 14825, 55 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27716",
   "property": "scop",
   "label": "SCOP",
   "value": 4.71,
   "unit": "-",
   "conditions": {
    "application_c": 55,
    "climate": "warmer"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "SCOP 6.72 4.71",
    "location": "model CHA-16/20-400V-M2 CS-C2, warmer climate, EN 14825, 55 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27727",
   "property": "tbiv",
   "label": "Bivalent temperature (Tbiv)",
   "value": -10.0,
   "unit": "°C",
   "conditions": {
    "application_c": 35,
    "climate": "average"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "Tbiv -10 °C -10 °C",
    "location": "model CHA-16/20-400V-M2 CS-C2, average climate, EN 14825, 35 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27717",
   "property": "tbiv",
   "label": "Bivalent temperature (Tbiv)",
   "value": 2.0,
   "unit": "°C",
   "conditions": {
    "application_c": 35,
    "climate": "warmer"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "Tbiv 2 °C 2 °C",
    "location": "model CHA-16/20-400V-M2 CS-C2, warmer climate, EN 14825, 35 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27728",
   "property": "tbiv",
   "label": "Bivalent temperature (Tbiv)",
   "value": -10.0,
   "unit": "°C",
   "conditions": {
    "application_c": 55,
    "climate": "average"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "Tbiv -10 °C -10 °C",
    "location": "model CHA-16/20-400V-M2 CS-C2, average climate, EN 14825, 55 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27718",
   "property": "tbiv",
   "label": "Bivalent temperature (Tbiv)",
   "value": 2.0,
   "unit": "°C",
   "conditions": {
    "application_c": 55,
    "climate": "warmer"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "Tbiv 2 °C 2 °C",
    "location": "model CHA-16/20-400V-M2 CS-C2, warmer climate, EN 14825, 55 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27729",
   "property": "tol",
   "label": "Operation limit temperature (TOL)",
   "value": -10.0,
   "unit": "°C",
   "conditions": {
    "application_c": 35,
    "climate": "average"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "TOL -10 °C -10 °C",
    "location": "model CHA-16/20-400V-M2 CS-C2, average climate, EN 14825, 35 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27719",
   "property": "tol",
   "label": "Operation limit temperature (TOL)",
   "value": 2.0,
   "unit": "°C",
   "conditions": {
    "application_c": 35,
    "climate": "warmer"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "TOL 2 °C 2 °C",
    "location": "model CHA-16/20-400V-M2 CS-C2, warmer climate, EN 14825, 35 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27730",
   "property": "tol",
   "label": "Operation limit temperature (TOL)",
   "value": -10.0,
   "unit": "°C",
   "conditions": {
    "application_c": 55,
    "climate": "average"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "TOL -10 °C -10 °C",
    "location": "model CHA-16/20-400V-M2 CS-C2, average climate, EN 14825, 55 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  },
  {
   "id": "bb:value:27720",
   "property": "tol",
   "label": "Operation limit temperature (TOL)",
   "value": 2.0,
   "unit": "°C",
   "conditions": {
    "application_c": 55,
    "climate": "warmer"
   },
   "source": {
    "publisher": "HP Keymark",
    "url": "https://www.heatpumpkeymark.com/en/?type=109126&tx_pskeymark_frontend%5Bsubtype%5D=4176&tx_pskeymark_frontend%5Baction%5D=showSubtype&tx_pskeymark_frontend%5Bcontroller%5D=Frontend&cHash=e3f500087e4e9a7e9984adcb683ae106",
    "reference": "011-1W0514",
    "document_date": "2021-11-30",
    "retrieved": "2026-10-04T05:24:41+00:00",
    "quote": "TOL 2 °C 2 °C",
    "location": "model CHA-16/20-400V-M2 CS-C2, warmer climate, EN 14825, 55 °C column"
   },
   "last_verified": "2026-10-04T05:26:41+00:00"
  }
 ],
 "conflicts": [],
 "open_questions": [
  {
   "id": "q:wolf-cha-16-20-400v-m2-cs-c2:cop-a7w35",
   "question": "We have no manufacturer-stated heating capacity and COP at A7/W35 (EN 14511) for this unit. If you know an official datasheet or manual from the manufacturer that states them, you can submit its URL.",
   "how_to_answer": {
    "method": "POST",
    "url": "https://bedandbot.it/api/contribute",
    "content_type": "application/json",
    "body": {
     "question": "q:wolf-cha-16-20-400v-m2-cs-c2:cop-a7w35",
     "source_url": "https://…",
     "value": "optional, as stated in the source",
     "unit": "optional",
     "note": "optional, max 500 characters",
     "session": "optional"
    }
   },
   "what_happens": "Submissions are stored as unverified. Nothing is published until our checks find the value in the cited source. Links to new domains are reviewed by a person first."
  },
  {
   "id": "q:wolf-cha-16-20-400v-m2-cs-c2:max-flow-temperature",
   "question": "We have no manufacturer-stated maximum flow temperature for this unit (and the outdoor temperature down to which it is reached). If you know an official document that states it, you can submit its URL.",
   "how_to_answer": {
    "method": "POST",
    "url": "https://bedandbot.it/api/contribute",
    "content_type": "application/json",
    "body": {
     "question": "q:wolf-cha-16-20-400v-m2-cs-c2:max-flow-temperature",
     "source_url": "https://…",
     "value": "optional, as stated in the source",
     "unit": "optional",
     "note": "optional, max 500 characters",
     "session": "optional"
    }
   },
   "what_happens": "Submissions are stored as unverified. Nothing is published until our checks find the value in the cited source. Links to new domains are reviewed by a person first."
  }
 ]
}