Wolf CHA-10/400V

air-to-water monobloc · refrigerant R290 · 3x400V 50Hz · family CHA-Monoblock

Machine-readable: https://bedandbot.it/p/wolf-cha-10-400v.json

PropertyConditionsValueSource
Seasonal space heating energy efficiency (ηs)average climate, 35 °C application191 %HP Keymark 011-1W0381
“η s 191 % 141 %”
Seasonal space heating energy efficiency (ηs)colder climate, 35 °C application177 %HP Keymark 011-1W0381
“η s 177 % 135 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 35 °C application272 %HP Keymark 011-1W0381
“η s 272 % 185 %”
Seasonal space heating energy efficiency (ηs)average climate, 55 °C application141 %HP Keymark 011-1W0381
“η s 191 % 141 %”
Seasonal space heating energy efficiency (ηs)colder climate, 55 °C application135 %HP Keymark 011-1W0381
“η s 177 % 135 %”
Seasonal space heating energy efficiency (ηs)warmer climate, 55 °C application185 %HP Keymark 011-1W0381
“η s 272 % 185 %”
Rated heat output (Prated)average climate, 35 °C application7.58 kWHP Keymark 011-1W0381
“Prated 7.58 kW 7.40 kW”
Rated heat output (Prated)colder climate, 35 °C application8.78 kWHP Keymark 011-1W0381
“Prated 8.78 kW 8.17 kW”
Rated heat output (Prated)warmer climate, 35 °C application8.57 kWHP Keymark 011-1W0381
“Prated 8.57 kW 8.64 kW”
Rated heat output (Prated)average climate, 55 °C application7.4 kWHP Keymark 011-1W0381
“Prated 7.58 kW 7.40 kW”
Rated heat output (Prated)colder climate, 55 °C application8.17 kWHP Keymark 011-1W0381
“Prated 8.78 kW 8.17 kW”
Rated heat output (Prated)warmer climate, 55 °C application8.64 kWHP Keymark 011-1W0381
“Prated 8.57 kW 8.64 kW”
Refrigerant charge—3.4 kgHP Keymark 011-1W0381
“Mass of Refrigerant 3,400 kg”
SCOPaverage climate, 35 °C application4.86 HP Keymark 011-1W0381
“SCOP 4.86 3.60”
SCOPcolder climate, 35 °C application4.5 HP Keymark 011-1W0381
“SCOP 4.50 3.44”
SCOPwarmer climate, 35 °C application6.88 HP Keymark 011-1W0381
“SCOP 6.88 4.71”
SCOPaverage climate, 55 °C application3.6 HP Keymark 011-1W0381
“SCOP 4.86 3.60”
SCOPcolder climate, 55 °C application3.44 HP Keymark 011-1W0381
“SCOP 4.50 3.44”
SCOPwarmer climate, 55 °C application4.71 HP Keymark 011-1W0381
“SCOP 6.88 4.71”
Bivalent temperature (Tbiv)average climate, 35 °C application-10 °CHP Keymark 011-1W0381
“Tbiv -10 °C -10 °C”
Bivalent temperature (Tbiv)colder climate, 35 °C application-17 °CHP Keymark 011-1W0381
“Tbiv -17 °C -17 °C”
Bivalent temperature (Tbiv)warmer climate, 35 °C application2 °CHP Keymark 011-1W0381
“Tbiv 2 °C 2 °C”
Bivalent temperature (Tbiv)average climate, 55 °C application-10 °CHP Keymark 011-1W0381
“Tbiv -10 °C -10 °C”
Bivalent temperature (Tbiv)colder climate, 55 °C application-17 °CHP Keymark 011-1W0381
“Tbiv -17 °C -17 °C”
Bivalent temperature (Tbiv)warmer climate, 55 °C application2 °CHP Keymark 011-1W0381
“Tbiv 2 °C 2 °C”
Operation limit temperature (TOL)average climate, 35 °C application-22 °CHP Keymark 011-1W0381
“TOL -22 °C -22 °C”
Operation limit temperature (TOL)colder climate, 35 °C application-22 °CHP Keymark 011-1W0381
“TOL -22 °C -22 °C”
Operation limit temperature (TOL)warmer climate, 35 °C application-22 °CHP Keymark 011-1W0381
“TOL -22 °C -22 °C”
Operation limit temperature (TOL)average climate, 55 °C application-22 °CHP Keymark 011-1W0381
“TOL -22 °C -22 °C”
Operation limit temperature (TOL)colder climate, 55 °C application-22 °CHP Keymark 011-1W0381
“TOL -22 °C -22 °C”
Operation limit temperature (TOL)warmer climate, 55 °C application-22 °CHP Keymark 011-1W0381
“TOL -22 °C -22 °C”

Open questions

Values are copied from the cited source, with the quoted text they were read from. Seasonal values: EN 14825 (climate × application). Check the source before relying on a value.